18th Edition: How Will RCD Selection Work?

18th Edition: How Will RCD Selection Work?

Chaz Andrews, Technical Manager at Doepke UK, discusses the latest updates regarding consumer units and RCD use.

Type AC residual current protection has been applied in UK domestic premises, with little consideration for the nature of appliances and loads connected downstream of the RCD. The impact of increased leakage currents can result in unwanted tripping, which results in other safety complications – loss of lighting and supplies for essential equipment.

These issues have been addressed in the 18th Edition and will need to be incorporated in to domestic consumer units, as applicable to the revised regulations.

Regulation 531.3.2 deals with unwanted tripping and the requirements for reliable performance. Regulation 531.3.3 covers the selection of different types of RCD, based on the type of residual current, and applies to all installations.

Why should we improve safety in electrical installations?

Electrical Safety First highlight that far greater demands are placed on domestic electrical installations than at any time, with more electrical appliances per head and increased complexity leading to increased risk of electrical accidents… β€œGovernment statistics show that electricity causes more than 20,000 fires a year – almost half of all accidental UK house fires. Each year, about 70 people are killed and 350,000 are seriously injured due to an electrical accident in the home”. In their words…. β€œIt’s easy to make an electrical circuit work – it’s far harder to make the circuit work safely”.

RCD selection: what the 18th Edition says

Regulation 531.3 (formally 531.2) covers the selection of RCDs for fault protection by automatic disconnection of the supply. There are several changes in this section giving more detailed requirements and advice on selection of RCDs to improve the quality and safety of domestic installations.

531.3.2 Unwanted tripping

LED lighting, PCs, TV power supplies or any equipment containing capacitors (just about everything these days) produce higher leakage currents than conventional loads we had in our old homes. Customers should be advised of the possibility of unwanted tripping, where too many appliances are connected downstream of one RCD.

Allow for the reliable provision of lighting circuits in all installations and any medical equipment for home treatment/diagnostics, stairlifts etc. (See 314 Division of Installation). Domestic Lighting Circuits must now incorporate RCD protection <30 mA – see Regulation 411.3.4.

RCD protected circuits:

Consider any earth leakage current likely to occur in normal operation, to reduce the chance of unwanted tripping. Examples are given in Table 1.

  • The sum of the leakage currents shall not exceed 30% of the RCD residual current. Note 2 reminds us that RCDs are designed to trip if the residual current is > 50% Iβˆ†n
  • Short time-delayed* transient resistant 30 mA RCDs with 5 x Iβˆ†n <40 ms characteristic can be used to reduce unwanted tripping associated with capacitors charging in power supplies.

*Not to be confused with Selective/Timed delay RCDs which are not suitable for 30 mA applications.

Equipment with leakage currents > 3.5 < 10 mA must be permanently connected (see 543.7.1.201).

531.3.3 Types of RCD:

Appliances such as certain types of washing machine, induction hobs, LED lighting, power supplies for TV, PC and AV equipment, speed control on pumps etc. can produce residual currents that are not compatible with Type AC RCDs.

This Regulation specifies the different Types of RCD based on their ability to deal with various types of residual current. The appropriate RCD shall be selected from the following type: AC, A, F or B. See Table 2 for a summary of the characteristics given in 531.3.3. Note: Type EV is related to Reg. 722.531.2.101 

 

Incorporating these requirements into consumer units

Most equipment using single phase SWM power supplies (PCs, TVs, games consoles and LED lamps) should be suitable for use with Type A RCDs. Some equipment, mainly related to kitchens and/or utility rooms, is designed for connection to circuits protected by Type F RCDs.

These appliances are becoming more common as older appliances are replaced with energy efficient ones. This is likely to have a greater impact on new builds, where appliances are supplied as part of the fixtures and fittings. The house builder is also responsible for the electrical specification and installation certificates for each property.

What are the risks if you use Type A instead of Type F?

Residual currents generated by the equipment <1kHz cannot be detected and they may also result in the RCD overheating/non-tripping for 50Hz residual currents.

For lighting circuits incorporating LED lamps, consider the individual LED driver’s inrush current and leakage current. The high transient currents that flow when the LED drivers are powered up (typically 50 – 80 x lamp current), may cause unwanted tripping if there are too many lamps on one circuit (standard RCDs – maximum 250A 8/20Β΅s). If this is likely to be an issue, restrict the number of lamps per circuit or use transient resistant RCD such as Type AKV or Type F – see Table 2.

The leakage current is harder to determine as it will be linked to the type of fitting, type of lamp and the location e.g. in a bathroom or other humid environments. These two areas require practical experience and advice from the LED lamp manufacturers to help installers design reliable lighting installations, when associated with 30mA RCD protected circuits.

Design for safe and reliable operation

In a modern installation it is unlikely that Type AC RCDs can be used safely, unless the circuit is restricted to the use of general purpose equipment, such as resistive heating and lighting loads.

The example consumer unit (pictured) contains a single module Type A RCBO for lighting circuit with room for other RCBOs, alarm circuits etc. Type F RCCB protected circuits for kitchen, utility rooms plus any other circuits and Type A RCCB for circuits supplying family rooms and bedrooms, in line with the requirements of the 18th Edition regulations.

Further information about Doepke’s range of circuit protection solutions can be found on at: www.doepke.co.uk

 

Related posts