Need help with cracking those EICR codes? The technical team at NAPIT, with the help of the 18th Edition Codebreakers publication, answer your latest coding queries. Click on the photos for a closer look!
WILLIAM CULLETON: “MY ELECTRICS TRIP WHEN IT RAINS!”
These extension lead connections were discovered during periodic inspection and testing. Strictly speaking, portable appliances and flexible cables connected via plugs are not part of the electrical installation that is governed by BS 7671.
Obviously, the means of connection to the external socket-outlet utilising a multi-way adaptor is preventing the cover IP rated socket-outlet from being closed to remove the effects of moisture or water penetration. Further complications arise by utilising an extension lead which is not suitable for external use.
The client query about the installation tripping when it rains shows a lack of understanding of basic electrical safety.
The area of concern when having these types of equipment plugged into the electrical installation is that they are portable and may not be connected or in place when the periodic inspection and testing is carried out. As a result, they’re at risk of not being discovered.
Therefore, the classification code would be a C2, Potentially dangerous, urgent remedial action required due to the lack protection for electrical equipment connected to the electrical installation.