We’re back with another #caughtoncamera ! This one was sent in by Simon Geraghty “When the customer says he canโ€™t understand why the cooker hood doesnโ€™t work !!”

Check out this shocking #caughtoncamera sent over by Kevin Smith “This CU change could not have been carried out by an electrician! Undersized cables for OCPDs i.e. 2.5mm off a 32A feeding 5+ kW accumulated loads and 6mm T&E mains tails off a 100A DNO fuse. No grommets, no fire rating, no circuit identification. Conductors not securely terminated. Unsheathed single insulated cables outside of enclosure. Dual RCDs that donโ€™t operate before the upstream 63A 30mA covering whole installation. No main bonding, multiple metallic water pipes entering from the ground. Earthing conductor to electrode poor connection.”
  • KEVIN SMITH 1
  • KEVIN SMITH 2
  • KEVIN SMITH 3
  • KEVIN SMITH 4

A scary #caughtoncamera we received recently from Terry Homer – “Wouldnโ€™t life be so much easier if we could just do this!โ€