Consumer unit safety (BS EN 61439-3): The importance of requesting Type Test certification | Contactum

Consumer unit safety (BS EN 61439-3): The importance of requesting Type Test certification | Contactum

Why it is important to request Type Test certification when sourcing a consumer unit? The experts at Contactum help to shed some light.

Within BS7671 the wiring regulations, Regulation 421.1.201 states that ‘within domestic (household) premises, consumer units and similar switchgear assemblies must comply with BS EN 61439-3 …’

In this article we aim to look into some of the compliance requirements of BS EN 61439-3 and the responsibilities manufactures have to fulfil before certification is granted. As such, Contactum is proud to be able to share excerpts taken directly from its Defender 2 test reports.

Certification to BS EN 61439-3 requires a variety of tests to be performed, with certification only granted on successful completion of each test. These tests are onerous and designed to prove the unit is able to perform way past its normal expected operational design characteristics.

They are as follows:

– Resistance to corrosion

– Verification of resistance of insulating materials to abnormal heat and

– Fire due to internal electric effects

– Verification of protection against mechanical impact (IK code)

– Marking l Degree of protection (IP code)

– Clearance and creepage distances

– Effective earth continuity between the exposed conductive parts of the assembly and the protective circuit

– Short-circuit withstand strength of the protective circuit

– Conditional short-circuit test

– Incorporation of switching devices and components

– Internal electrical circuits and connections

– Terminal for external conductors

– Power frequency withstand voltage test

– Impulse withstand voltage test

– Temperature-rise tests

– Short-time withstand current test

– Short-circuit withstand strength test. 16 ka test with fuse (Annex ZB)

– Dielectric verification

– Electromagnetic compatibility

– Mechanical operation

Some of the tests are more critical than others, but all are mandatory for the unit to be certificated.

So, let’s now take a look at the report details from some of the more arduous tests carried out on our Defender 2 units:

Resistance to corrosion

The test was performed according to BS EN 61439-3, Clause 10.2.2.2., and is carried out on a representative enclosure with a degree of severity ‘A’.

The test consists of applying 6 x cycles of 24 hours each to the damp heat cycling test (according to IEC 60068-2-30:2005 (test Db)) at a temperature of 40ºC and relative humidity of 95%. After this, a further 2 x cycles of 24 hours each to salt mist (according to IEC 60068-2-11) at a temperature of 35ºC were applied.

After the test, the enclosure is washed in running tap water for five minutes, in distilled or demineralized water then shaken or subjected to an air blast to remove any water droplets.

  • FIG 1(a)
  • FIG 1(b)

Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects

The test, carried out on panel #1, is performed according to BS EN 61439-3, Clause 10.2.3.2.

The test specimen is conditioned for at least 24 hours at a temperature between 15ºC and 35ºC and a relative humidity between 45% and 75%. Once removed from the conditioning atmosphere, the test specimen is tested within 30 minutes.

The wrapping tissue and the wooden board to be placed underneath the test specimen are specified in 5.3 of IEC 60695-2-10. They are conditioned for a minimum of 24 hours at a temperature between 15ºC and 35ºC and a relative humidity between 45% and 75%.

The test specimen is considered to have withstood this test if there is no ignition, or if all the following situations apply:

a) The longest sustained and continuous flames or glowing of the test specimen after removal of the glow wire extinguish within 30 seconds;

b) The specimen is not totally consumed; and

c) There is no ignition of the wrapping tissue.

  • FIG 2(a)
  • FIG 2(b)

6.2. Test parameters

The temperatures are as follows:

– 960 ± 15ºC for insulating materials supporting live elements (terminal connectors).

– 650 ± 10ºC for insulating materials not supporting live elements (cable support and isolating board).

Degree of protection (IP code)

This test, carried out on panel #1, is performed according to BS EN 61439-3, Clause 10.3.

The verification of the degree of protection of the enclosure is conducted in accordance with the standard IEC 60529:1989+AMD1:1999+AMD2:2013.

The protection against access to dangerous areas and access of foreign particles, as well as ingress of water, is verified, and the IP code IP2XC is then assigned. IP4X is also assigned, but only for the top of the unit.

Protection against access to dangerous areas

IP4X in the top, according to the first characteristic 4, the access probe of 1mm diameter and 100mm length applied with a force of 1 N ± 10% shall not give access to dangerous mechanical or live parts.

Temperature-rise tests

This test was performed according to BS EN 61439-3, Clause 10.10.2.3.5.

The loads distribution in the different tested panels, and the cables cross section can be seen in the table (pictured below).

The temperature of the different parts was measured by thermocouples type K. When this test is performed, a load is connected to the outgoing breakers, as per the table. The temperature is monitored for heat rise.

The result: we have the full rating of the board without derating the outgoing circuits.

Short-time withstand current test

This test was performed according to BS EN 61439-3, Clause 10.11.

The full current was applied to the main horizontal busbar. The enclosure is connected to earth by a fuse element (copper wire of 0.8mm diameter and 50mm long) for the detection of fault currents.

The supply is a 35mm2 copper cable connected to each side of the main busbar, with a total cable length of 2.35m.

Test parameters – Main circuit

Itest (RMS): 10 kA
Itest (peak): 17 kA
Cos φ: 0.5
Time: 0.1 s

Short-circuit withstand strength test. 16 ka test with fuse (Annex ZB)

This test was performed according to BS EN 61439-3, Clause 10.11.5. The test object is placed in a support with cotton of about 34 g/m2 placed in all the openings that might be susceptible of emitting gases.

The test sequence is as follows: O-t-CO

Where:
O: Breaking operation.
CO: Making operation followed by a breaking operation.
t: Interval between two successive short-circuit operations.

After the test the insulating resistance must be measured with the following limits:

– 0.1 MΩ between the incoming terminals of the protective device, in open position, and the output terminal.

– 0.25 MΩ between the protective device and the earth.

The correct working of the residual current device is verified by supplying with a voltage that is 0.85 times the nominal voltage. The test is performed to units of maximum and minimum rating for any different outgoing unit tested.

Annex ZB of BS EN 61439-3 is a verification of the consumer unit to withstand a 16kA fault. This is a specific requirement for consumer units used within UK installations.

When choosing Defender 2, users are guaranteed a quality, safe and well designed consumer unit which meets the stringent requirements of BS EN 61439-3.

Browse the Contactum Defender 2 brochure here

Related posts