Bureau Veritas warns of rising number of AC type Residual current devices (RCDs) being adversely affected by direct currents (DC) from electronic devices and renewable energy sources.
Their warning follows on from the 18th Edition including updated guidance on the use of various types of RCDs.
It comes amid the growing use of RCDs over the years, with AC Type RCD’s often promoted as the first choice, particularly since 2001 where the 17th edition (Amendment 1) directly stated AC Type RCDs should be used for sockets that might supply outdoor equipment.
However, according to electrical safety expert Bureau Veritas, as more and more homes, commercial and industrial sites are now using electronic equipment and installing renewables such as solar PV, many of these RCDs may well be not fit for purpose – putting an increasing number of people at risk.
Michael Kenyon, Technical Manager at Bureau Veritas, says: “Modern electrical installations are now more than ever incorporating technologies and products that manipulate the current wave forms. These devices such as Solar PV and electric vehicle chargers could be leaking (Direct Current) back into the electrical system and saturating the iron core of the AC type RCDs which are not designed to handle it.
As an independent electrical specialist, Bureau Veritas suggests the industry, instead, looks at using A or B type RCDs that are specifically designed to offer protection against alternating and pulsating direct – as stated in the recent rewrite of 531.3 of BS7671.
Michael adds: “The rewrite of 531.3 has certainly led to an increased awareness of the different type of RCDs on the market but in terms of promoting best practice – at the moment it just doesn’t go far enough in recommending the use of A type RCDs.
In fact, regulation (531.3.3) still states that for general purposes, Type AC RCDs should be used coupled with disincentive that Type A RCDs are still much less readily available.”
For more information on Bureau Veritas visit: https://www.bureauveritas.co.uk/