Remarkably, it’s now a year since the publication of the 18th Edition wiring regulations. ECA’s Senior Technical Support Engineer Gary Parker highlights some of the more challenging changes, and those December 2018 corrections.
The 18th Edition of the IET Wiring Regulations (BS 7671:2018) has been in full effect for several months now. The blue book was first published in July 2018, to allow the industry six months to get to grips with the changes before they came into full effect on 1 January 2019.
However, almost a year later, some 18th Edition changes are proving harder to implement than others. Below is a summary of the most frequently asked-about changes on the ECA Member helpline, with a handy note of which section to turn to in the 18th Edition for each one.
An important set of corrections was also published in December 2018. More on this below…
Residual current devices (RCDs)
Chapter 41 – protection against electric shock, Regulation 411.3.4
The application of RCDs has been expanded and revised for certain situations. The Regulation now requires that, within domestic premises, additional protection by an RCD shall be provided for AC final circuits supplying luminaires.
This was new, and most likely a response to the many new ways we now use lighting in our homes, with the introduction of LEDs, advanced lighting displays, and the fact that consumers are now able to purchase luminaires and put them up themselves.
Another change sees the period between testing RCDs (by pushing the ‘T’ or ‘Test’ button) increased from ‘quarterly’ to ‘six-monthly’, which means that the task can be conveniently done when the clocks are changed.
Arc fault detection devices (AFDDS)
Chapter 42 – protection against thermal effects, Regulation 421.1.7
This new Regulation recommends that Arc Fault Detection Devices are installed to help mitigate the risk of fire in AC final circuits in the event of arc faults.
They are recommended for premises with sleeping accommodation, and locations with risk of fire due to the nature of processed or stored materials, such as barns, woodworking shops, or stores of combustible materials.
Surge protection devices (SPDs)
Chapter 44 – Protection against voltage disturbances and electromagnetic disturbances, Regulation 443.4
This amended section now stipulates that protection against overvoltage by means of Surge Protection Devices (SPDs) has to be provided. This is applicable where the consequence of an overvoltage would result in serious injury or loss of life, serious disruption of public services, interruption of industrial activity, or if it would affect a large number of co-located individuals.
Electric vehicles (EVs)
Section 722 – electric vehicle charging installations
These changes are relatively small, but they will have big implications. Particularly for charging points installed at a dwelling, outside a building, on a TN-C-S earthing system. As with other changes, these are to keep the UK’s standards in tandem with the technical intent of worldwide standards.
In the 18th Edition, the option to use a protective multiple earthing (PME) facility has been reduced. There are ways that PME can be used, but these are often difficult to achieve. Therefore, most installations will rely on separation of the earthing system and making the EV a TT system (using an electrode in the ground).
Newly recognised types of RCDs are specifically picked up on in section 722 for EVs, but general awareness of these in the wider industry is very low. The new devices are electronic in nature and have a different reaction to circuits containing power electronics that can distort the waveform. The industry and its customers are only just becoming aware of these products, the costs are high in comparison to existing devices, and availability is limited.
December’s Corrigendum
In December 2018, 11 corrections to the 18th Edition were published in a Corrigendum. These are, in summary:
- Five labels oversized in Section 514
- A new colour is available to use to identify a functional earthing conductor
- Update regarding alignment of a zone in Figure 701.1f to match the words detailed in Regulation 701.32.3
- In medical locations of group 1 and group 1, a minimum of 2 lighting circuits shall be provided from separate sources of supply
- Change to the zone markings in Fig 701.1f
- Appendix 4 last row of the table covers 90 ºC ‘thermosetting’ cables, and not as thermoplastic cables
There are a range of other changes within the 18th Edition. You can find out more about the changes, relevant training and other industry updates by going to: www.eca.co.uk/Project18