Kirsty Johnson of Surge Protection Devices looks at the surge protection requirements for EV chargers in the wake of Amendment 2 to the 18th Edition.
We’re already aware of the effects and challenges of installing EV chargers regarding RCD requirements and earthing, but how much consideration is given to the surge protection requirements of these installations?
Although surge protection is not mentioned specifically in Section 722 of the wiring regulations, Section 700 states that the absence of reference to the exclusion of a part, a chapter, a section or a regulation means that the corresponding general regulations are applicable. This means that in terms of surge protection, Section 443 applies.
To meet the requirements of Section 443 in the second amendment of the BS 7671:2018 wiring regulations, such protection must be installed, where overvoltage could:
i. Result in serious injury to, or loss of human life, or
ii. Result in failure of a safety service, as defined in part 2, or
iii. Result in significant financial loss or data loss.
Breaking these requirements down, indent #1 can apply to EV charger installations in some circumstances. It is common practice now to see EV chargers contacting loss of neutral safety devices, which are used to disconnect the car charger from the PME supply in the event of a loss of neutral to the installation.
These devices are used because of the worst-case scenario of a loss of neutral, which could lead to the car itself becoming a live conductor, possibly causing injury or death.
Loss of neutral detection devices are there to notice the rise in voltage which follows a loss of neutral and subsequently disconnect the supply. Unlike a surge device, however, they detect long duration overvoltage over a period of seconds, ensuring they’ll not be activated by a surge.
Although the short duration overvoltage won’t cause nuisance tripping of the device, it can instead degrade the device and cause damage. This could lead to the loss of neutral device failing to disconnect the car in the event of a fault, leading to a potential risk to life.
Therefore, if an EV charger is being installed where this technology is utilised, an SPD should be installed.
I don’t see any implications that indent #2 would apply to the installation of EV chargers, but indent #3 certainly can apply in more commercial EV charging installations, where the sensitive components within the EV charger itself can be damaged by overvoltage and cause a significant financial loss to the owner of the chargers.
“For all other cases SPDs shall be fitted to protect against transient overvoltages, unless the owner of the installation declines such protection and wishes to accept the risk of damage to both wiring and equipment as tolerable.”
By their very nature, EV chargers are both sensitive (limited impulse withstand capacity) and exposed to overvoltage. In fact, quite a few EV charger manufacturers will specify that an SPD should be installable or mention surge protection in the warranty details.
With the current trend of installing EV chargers, without considering the cost of the car that is connected to them, the installation of a surge protection device to provide additional protection would be a sensible idea in any installation.
We’ll also have to give consideration to the installation that the EV charger is fed from. We have to remember that any cable that enters an installation can bring with it the risk of overvoltage, the effects of nearby lightning strikes and switching surges that can cause damage to the installation along with the EV charger unit.
So, by installing an SPD on your EV charger distribution board, you will also be protecting the installation from any overvoltage that could be transmitted from the EV charger, as well as protecting the EV charger itself.
External lightning protection
I couldn’t finish this article without also giving a mention to installations with external lightning protection systems. EV installations are leading to cables being exported from distribution boards to external circuits.
When a building has an external lightning protection system, we have to consider lightning protection zones. Any cable that crosses from lightning protection zone 0 (outside) to lightning protection zone 1 (inside) requires a type 1 SPD, as that cable can allow lightning to enter the structure.
This mean that if you’re installing an EV charger on a building with a lightning protection system, when a cable is taken from a distribution board to supply the charger, a type 1 SPD will be required on the distribution board to meet the requirements of BS EN 62305.