Changes in Amendment 2 that will affect surge protection | Surge Protection Devices

Changes in Amendment 2 that will affect surge protection | Surge Protection Devices

Following the release of Amendment 2, Kirsty Johnson of Surge Protection Devices looks at some of the changes that will affect surge protection

Section 443

As expected, the wording has significantly changed for section 443 from both the first edition of BS7671:2018 and from the proposed DPC that was released towards the end of 2020.

Two significant changes are:

● The removal of the risk assessment. This will mean that the installation of surge protection devices can no longer be decided via a calculation.

● The removal of the special dispensation for single dwellings. They are now to be considered along with all other electrical installations.

Both changes now mean that regulation 443.4.1 must be considered for every installation.

Protection against transient overvoltages shall be provided where the consequence caused by overvoltage could:

i. Result in serious injury to, or loss of human life, or

ii. Result in failure of a safety service, as defined in part 2, or

iii. Result in significant financial loss or data loss

For all other cases SPDs shall be fitted to protect against transient overvoltages, unless the owner of the installation declines such protection and wishes to accept the risk of damage to both wiring and equipment as tolerable.

The requirement to install SPDs where the consequences could result in serious injury to, or loss of human life is the same as previously stated in Amendment 1. Where we see a big shift, is in indent two, which requires an SPD to be installed where the consequences could result in the failure of a safety service as defined in part 2.

BS 7671 defines safety services as: “An electrical system for electrical equipment provided to protect or warn persons in the event of a hazard, or essential to their evacuation from a location”

This will mean that any distribution board supplying electrical equipment that would fall in to the definition of a safety service, as described previously, will require an SPD. Therefore, now that domestic installations are not exempt from these requirements, a smoke alarm that is supplied from a consumer unit, rather than a battery, must be protected by an SPD.

Indent three is similar to the previous requirement where an SPD should be installed where commercial or industrial activity could be interrupted, the requirement now is that an SPD shall be provided where the consequence caused by overvoltage could result in significant financial or data loss.

This leads on to the final requirements of the regulation:

For all other cases SPDs shall be fitted to protect against transient overvoltages, unless the owner of the installation declines such protection and wishes to accept the risk of damage to both wiring and equipment as tolerable.

The basic position of section 443 is now that SPDs shall be installed. In practical terms, most installations will have distribution boards that require surge protection due to the indents described, so it would only be distribution boards that did not require surge protection, as no circuits outlined in regulation 443.4.1 were present. Then a discussion is encouraged between the electrical designer and the client to ensure that no unacceptable losses occur from overvoltage, while also considering the requirements to protect against switching overvoltages from regulation 443.4.2.

Regulation 443.4.2: Protection against overvoltages shall be considered in the case of equipment likely to produce switching overvoltages or disturbances exceeding the applicable rated impulse voltage of equipment according to Table 443.2, e.g., where inductive or capacitive equipment, such as motors, transformers, capacitor banks, storage units or high current loads are installed.

Section 443 details where surge protection devices need to be installed, however, what is not clear is the type of device required. Generally, Type 2 SPDs will be used for most installations but type 1 devices will be needed in certain circumstances.

For all other circumstances, a Type 2 device will be sufficient to provide adequate protection for distribution boards. Where protection against overvoltages is required for specific equipment, a Type 3 device may be used to provide protection.

If the building has an external lightning protection system:

If the building has an overhead supply:

Section 712

As was shown in the DPC, we also have some changes to section 712, with respects to surge protection.

Regulation 712.443.101 states that where protection against transient overvoltage is required by section 443, such protection shall also be applied to the DC side of the PV installation.

This will mean that if the electrical installation requires surge protection to be fitted to comply with section 443, as discussed here, SPDs would now also need to be installed on the DC side of the installation to protect both the PV panels and the inverter.

When the inverter incorporates an SPD, it is only considered as fulfilling the SPD requirement if the manufacturer specifies its use for the DC side of the PV installation, otherwise, it will need an external SPD. Varistors included in the inverter are not considered an SPD. Surge protection devices designed for the use on the DC side of a PV system are designed to a different standard than SPDs used in low voltage installations. Although they are still described by using Type 1 and Type 2, as explained earlier, where Type 1 devices are to protect against direct lightning, it is extremely important that only devices designed for use on the DC side of a PV installation are used. All SPDs installed on the DC side of a PV installation shall comply with BS EN 61643-31.

Generally, the SPD will be a Type 2, unless the building has an external lightning protection system. When a PV system is installed within the protected volume of the LPS installation, the PV system should be separated from all parts of the LPS in accordance with BSEN 62305-3, which describes the calculation for the correct separation distance. If the separation distance is not met, then to BS EN 62305 a Type 1 DC surge protection device will be required to protect the installation from the effects of lightning.

Section 514

As expected, Amendment 2 has also given a regulation with regards to labelling the presence of SPDs within an installation.

Regulation 514.16.1 The presence of SPDs in an installation shall be indicated by an information notice at or near the relevant distribution board(s).

The requirements of this regulation need not be applied for domestic (household) premises or similar simple installations where the information is recorded on the appropriate certification for initial verification, complete with Guidance for Recipients as detailed in Appendix 6, and issued to the person ordering the work.

To get more details about the free CPD sessions on offer from Surge Protection Devices click here