Codebreakers #98

Codebreakers #98

Need help with cracking those EICR codes? The technical team at NAPIT, with the help of the 18th Edition Codebreakers publication, answer your latest coding queries. Click on the photos for a closer look!

KEVIN BAILEY: THIS WAS DISCOVERED ON A RECENT INSPECTION. JUST HIDE IT BEHIND A FRIDGE AND NO ONE WILL NOTICE…

  • CODEBREAKER 2A
  • CODEBREAKER 2B
  • CODEBREAKER 2C
  • CODEBREAKER 2D

Often when some form of alteration has been carried out on an electrical installation, and in this case a kitchen upgrade, existing accessories are not in the correct locations for the new appliances.

There are correct methods for connection of conductors and unfortunately covering open connectors with insulation tape and then covering with plaster is not one of them.

There is a lack of support or protection against abrasion for the cables, including the location of the concealed cables where they are no longer in the prescribed zones due to the removal of the accessories.

Therefore, the classification code would be a C2, Potential dangerous, urgent remedial action required due to the poor terminations.

Order your copy of NAPIT Codebreakers here

Catch up on previous Codebreaker articles here