Each month, our team of expert, technical engineers answer essential questions from NICEIC-certified businesses. Here we share some of the latest Amendment 4 queries.

Q: With higher risk residential buildings being removed, how will this affect Arc Fault Detection Devices (AFDDs) and the recommendation for thatched buildings?

A: There are two misapprehensions here that need clarifying.

Firstly, the term ‘higher risk residential buildings’ has simply been changed to ‘high rise residential buildings (HRRBs)’, so the AFDD requirement for those buildings has not been removed; the term has just been reworded. This is to differentiate the BS 7671 definition from that in the Building Safety Act because the Act is far more encompassing in terms of building safety regulation, whereas BS 7671 is just looking at AFDD requirements.

Secondly, thatched buildings come under Regulation 422.4, which outlines requirements for combustible construction materials and the propagation of fire. The AFDD regulation doesn’t mention thatched buildings.

Q: Where there’s no specification for AFDD protection within a battery energy storage system, would the selection of AFDDs to cover this circuit be recommended?

A: Currently, the regulatory requirement for AFDDs is only for socket-outlet circuits rated up to 32 amp in four building types: care homes, high rise residential buildings, houses in multiple occupation, and purpose-built student accommodation. It provides protection for these circuits based on not knowing what’s going to be plugged into them.

There is no requirement within BS 7671 to include AFDDs within a circuit used to supply battery energy storage systems.