How battery storage systems can safely operate in island mode

How battery storage systems can safely operate in island mode

Steve Humphreys, Technical Commercial Manager at NAPIT, explains how battery storage systems can safely operate in island mode. From isolators to earth electrodes and system referencing relays, he outlines the key components that ensure automatic disconnection of supply (ADS) protects essential circuits when the grid goes down. 

With so many battery inverters and all-in-one systems, it can be difficult for designers and installers to select a system that provides the required fault protection against electric shock in island mode.

Island mode occurs when the battery storage system operates independently from the main grid supply. When the grid supply is lost, the battery system supplies power to essential consumer loads, effectively creating an “island” of power.

This article looks at how fault protection through automatic disconnection of supply (ADS) can be achieved using three critical components operating in the correct sequence.

Island mode isolator

An island mode isolator is required to meet the requirements of Section 551 of BS 7671, that deals with low voltage generators and Regulation 21 of the Electricity, Safety, Quality and Continuity Regulations (ESQCR). Regulation 21 of the ESQCR states:

“Where a person operates a source of energy as a switched alternative to a distributor’s network, they shall ensure that that source of energy cannot operate in parallel with that network and where the source of energy is part of a low voltage consumer’s installation, that installation shall comply with British Standard Requirements.”

BS 7671 and Regulation 551.6.1 go into more detail on how to achieve this by stating:

Precautions shall be taken so that the generator cannot operate in parallel with the system for distribution of electricity to the public. Suitable precautions may include one or more of the following: 

  • An electrical, mechanical or electromechanical interlock between the operating mechanisms or control circuits of the changeover switching devices
  • A system of locks with a single transferable key
  • A three-position break-before-make changeover switch
  • An automatic changeover switching device with a suitable interlock
  • Other means providing equivalent security of operation

During island mode, the isolator must disconnect all live conductors, including the neutral, to prevent backfeeding into the grid and protect anyone working on the distribution system, such as line workers.

Relays alone do not meet the requirements of the ESQCR Regulations 21 and 22, or an appropriate British CENLEC or IEC Standards in BS 7671. The isolator must meet the requirements of BS 7671 and specifically Table 537.4.

The isolator could be integral to the inverter in the form of a contactor that complies with BS EN IEC 60947-4-1 or an external manual switching device complying with BS EN IEC 60947-3, see Fig 1.

Consumers earth electrode

In island mode the battery storage system will need to be provided with a means of earthing.

This is often overlooked in the design of systems that are capable of supplying back up power in the event of the grid supply being lost. It stands to reason that any essential loads being supplied during island mode still need to have fault protection.

BS 7671 tells us that during a loss of grid supply the distributors earth connection cannot be relied upon. This is stated in Regulation 551.4.3.2.1:

“Protection by automatic disconnection of supply shall not rely upon the connection to the earthed point of the system for distribution of electricity to the public when the generator is operating as a switched alternative to a TN system. A suitable means of earthing shall be provided”

This means that a consumer’s earth electrode shall be provided for TN systems, as shown in Fig 2.

The consumers earth electrode shall be connected to the main earthing terminal, and the earthing conductor shall be suitability sized in accordance with Chapter 54 of BS 7671.

In TT systems, the existing consumers earth electrode can be used if its suitability has been confirmed, i.e. stable with a low resistance (not exceeding 200 Ω).

System referencing relay

The system referencing relay, previously known as the neutral/earth bond relay, is a component part of the system that is integral to island mode operation. In island mode we cannot have two neutral connections to protective earth at the same time.

Ultimately this will help prevent circulating neutral currents, unwanted tripping of RCDs and reduce the risks for DNO engineers working on the network.

When the system moves into island mode, the system referencing relay closes to create a neutral/earth bond between the neutral of the essential circuits to be supplied by the battery storage system and earth, as shown in Fig 3.

The system referencing relay must:

  • Close immediately after the island mode isolator opens for island mode operation
  • Open immediately before the island mode isolator closes for connected operation

The system referencing relay contact should be rated to be capable of making or breaking the largest sum of the prospective currents from all sources capable of simultaneously operating in parallel.

The system referencing relay should be connected between neutral and protective earth as near to the output of the inverter as possible.

Bringing it all together

Now we have looked at these three parts of the system and explained what they do, we can bring them all together to show how they work in unison.

  1. Once the grid supply is lost, the island mode isolator will disconnect all live conductors
  2. The system referencing relay closes immediately after the island mode isolator opens (typically within a fraction of a second). This ensures only one neutral is connected to the protective earth
  3. The consumers earth electrode has now become our reference point between the neutral of any essential circuits to true Earth
  4. In island mode, a TN-S earthing arrangement has now been created

The diagrams in Fig 4 and Fig 5 show the differences between Connected and Island modes using TN-C-S and TN-S arrangements. For all connected mode supply earthing arrangements, it is recommended to switch to a TN-S earthing arrangement in island mode.

Where PME conditions apply in connected mode, these conditions will remain in island mode, because for TN-C-S and TN-S supplies the installation remains connected to the distributor’s means of earthing.

However, as stated earlier in Regulation 551.4.3.2.1, the suppliers earth connection cannot be relied upon in island mode, it may be lost or become unreliable, so the system needs a new, dedicated earth to protect against electric shock.

Now that we have an earth reference point in island mode, along with suitable protective devices, essential circuits being supplied by the battery storage system will have fault protection by automatic disconnection of supply (ADS).

A word of caution, some inverter manufacturers claim the consumer earth electrode and system referencing relay are unnecessary. This type of inverter may use a ‘floating voltage’ arrangement that is unearthed during island mode operation, similar to an IT system.

This type of system is not suitable for domestic battery storage systems and may violate BS 7671, The Electricity at Work Regulations (EAWR) and The Electricity Safety, Quality and Continuity Regulations (ESQCR).

Conclusion

Essential circuits being supplied during island mode still need to have fault protection. Therefore, designers, installers and inspectors need to consider how fault protection is achieved during island mode operation of battery storage systems.

In this article we have shown how fault protection, using ADS, can be achieved in island mode by selecting the correct equipment and component parts and ensuring they operate correctly and safely.