NICEIC FAQs #8: NICEIC experts answer the latest technical queries

NICEIC FAQs #8: NICEIC experts answer the latest technical queries

Each month, our team of expert, technical engineers answer essential questions from NICEIC-certified businesses. Here we share some of the latest queries.

Q: For a new installation, any defect or omission revealed during the inspection and testing shall be?

a) recorded on the EIC

b) corrected

c) reported to customer

d) recorded as a “LIM”

A: The answer is b) corrected Regulation 644.1.1 states that “For a new installation, any defect or omission revealed during the inspection and testing shall be corrected before the Certificate is issued”.

Q: For compliance with BS 7671, can a 230 V AC fan be installed in Zone 1 of a domestic bathroom?

a) Yes

b) No

A: The answer is a) Yes Regulation 701.55 states that “In zone 1, only the following fixed and permanently connected current-using equipment shall be installed, provided it is suitable for installation in zone 1 according to the manufacturer’s instructions:” and the list includes “(viii) Ventilation equipment”.

Therefore, as the fan would fall within the definition of ventilation equipment, its installation would be compliant providing the manufacturer confirms that it is suitable for installation within zone 1 of a bathroom and the fan has a minimum degree of protection of IPX4 against external influences.

The required external influence is specified in regulation 701.512.2 which states that “Installed electrical equipment shall have at least the following degrees of protection: (i) In zone 0: IPX7 (ii) In zones 1 and 2: IPX4”.

Q: What is the minimum size of a supplementary bonding conductor if mechanical protection is not provided?

a) 2.5 mm²

b) 4.0 mm²

c) 6.0 mm²

d) 10.0 mm²

A: The answer is b) 4.0 mm²

Regulation 544.2.1 states that “A supplementary bonding conductor connecting two exposed-conductive-parts shall have a conductance, if sheathed or otherwise provided with mechanical protection, not less than that of the smaller protective conductor connected to the exposed-conductive-parts. If mechanical protection is not provided, its cross-sectional area shall be not less than 4.0 mm²”.